GV7RS150 | SCHNEIDER ELECTRIC | Thermal Magnetic Motor Circuit Breaker (90–150 A, 3P, 100 kA)

₹ 36,495.23

₹ 30,928.16 (Excl. Tax)


Warranty

We provide a 1-year warranty from the date of purchase for new products. Additionally, surplus / used items come with a 30-day warranty.

Delivery and Shipping

We aim to process orders within 5-7 business days. Shipping options vary by location with tracking provided; international shipping available with customs duties responsibility on customers.


Enquire Now
Interested in this product? Submit your enquiry by entering your details.

Manufacturer Part Number (MPN)

GV7RS150

Original Equipment Manufacturer

SCHNEIDER ELECTRIC

Descripción

Product Type 3‑pole thermal‑magnetic motor circuit breaker (manual starter)
Rated Operational Current (In) 90 A … 150 A adjustable
Utilisation Category AC‑3 (motor load) per IEC 60947‑4‑1
Rated Operational Voltage (Ue) 600 V AC; 690 V AC
Rated Insulation Voltage (Ui) 600 V AC; 750 V AC
Breaking Capacity (Icu) 100 kA @ 230‑240 V; 70 kA @ 380‑415 V; 65 kA @ 440 V; 10 kA @ 690 V AC
Rated Service Breaking Capacity (Ics) 100 % of Icu at all voltages
Trip Unit Technology Thermal‑magnetic
Motor Power Rating 55 kW to 110 kW depending on voltage (e.g. 55 kW @ 400 V, 90 kW @ 500 V, 110 kW @ 690 V)
Control Type Rocker lever manual operation
Connection Terminals Screw-clamp or lug, accepts bar or cable (up to 25 mm width)
Tightening Torque ~15 N·m on terminals
Power Dissipation ≈ 8.7 W per pole
Mechanical / Electrical Durability 40,000 cycles mechanical; 20,000 cycles electrical on AC‑3
Maximum Operating Rate 25 switching operations/hour
Dimensions (H×W×D) 161 × 105 × 111 mm
Weight ~2.02 kg
Rated Impulse Withstand Voltage (Uimp) 8 kV
Protection / Isolation Phase-failure sense; meets isolation standards IEC 60947‑1
Standards & Certifications IEC/EN 60947‑1, ‑2, ‑4‑1; UL 508; CE; VDE; CCC; DNV
IP Protection IP40 (body); IP40/45 with terminal shrouds
Shock / Vibration 15 g @ 20 ms; 2.5 g @ 25 Hz per IEC 60068‑2
Operating Temperature −25 °C … +70 °C (open mounted)
Storage Temperature −55 °C … +95 °C
Certifications / Markings Green Premium: No; RoHS / REACh compliant
SCHNEIDER ELECTRIC

GV7RS150 | SCHNEIDER ELECTRIC | Thermal Magnetic Motor Circuit Breaker (90–150 A, 3P, 100 kA)

₹ 30,928.16
Product Type 3‑pole thermal‑magnetic motor circuit breaker (manual starter)
Rated Operational Current (In) 90 A … 150 A adjustable
Utilisation Category AC‑3 (motor load) per IEC 60947‑4‑1
Rated Operational Voltage (Ue) 600 V AC; 690 V AC
Rated Insulation Voltage (Ui) 600 V AC; 750 V AC
Breaking Capacity (Icu) 100 kA @ 230‑240 V; 70 kA @ 380‑415 V; 65 kA @ 440 V; 10 kA @ 690 V AC
Rated Service Breaking Capacity (Ics) 100 % of Icu at all voltages
Trip Unit Technology Thermal‑magnetic
Motor Power Rating 55 kW to 110 kW depending on voltage (e.g. 55 kW @ 400 V, 90 kW @ 500 V, 110 kW @ 690 V)
Control Type Rocker lever manual operation
Connection Terminals Screw-clamp or lug, accepts bar or cable (up to 25 mm width)
Tightening Torque ~15 N·m on terminals
Power Dissipation ≈ 8.7 W per pole
Mechanical / Electrical Durability 40,000 cycles mechanical; 20,000 cycles electrical on AC‑3
Maximum Operating Rate 25 switching operations/hour
Dimensions (H×W×D) 161 × 105 × 111 mm
Weight ~2.02 kg
Rated Impulse Withstand Voltage (Uimp) 8 kV
Protection / Isolation Phase-failure sense; meets isolation standards IEC 60947‑1
Standards & Certifications IEC/EN 60947‑1, ‑2, ‑4‑1; UL 508; CE; VDE; CCC; DNV
IP Protection IP40 (body); IP40/45 with terminal shrouds
Shock / Vibration 15 g @ 20 ms; 2.5 g @ 25 Hz per IEC 60068‑2
Operating Temperature −25 °C … +70 °C (open mounted)
Storage Temperature −55 °C … +95 °C
Certifications / Markings Green Premium: No; RoHS / REACh compliant